DATASHEET
LA-HR1235W
REV 01 · 2026-07 · EN
AGM BATTERY · SERIE LA-HR1235WHigh-rate output
for demanding UPSs
12 V High Rate AGM battery (35 W at 15 min) with low internal resistance for high-demand UPSs.
AGM battery
TECHNOLOGY
Single model
LA-HR1235W
High Rate
SERIES
IDEAL FOR
High-demand UPS
Short discharges
Battery banks
15-min backup
QUICK DECISIONThe essentials, at a glance
Key figures for the range
VOLTAGE
12 V
CAPACITY
9,0 Ah / 35 W
SERVICE LIFE
5 years (float)
MAX. DISCHARGE
140 A (5 s)
TECHNICAL ADVANTAGESKey features
● 12 V, 35 W High Rate AGM battery for high-demand UPSs
● 5-year float service life at 25°C
● Low internal resistance AGM technology for extra energy delivery
● 30% increase in power output with 15 minutes of backup time
● Sealed, maintenance-free, highly reliable and with low self-discharge
● Maximum discharge current of 140 A for 5 seconds
● Maximum charging current of 2.7 A
● 6.3 mm F2 Faston terminal and ABS case with a flame-retardant option
● Suitable for data centres, UPS/EPS, telecoms, alarms and security
2-year battery warranty
Free pickup & return service
Only applicable in the Iberian Peninsula
www.laparaups.com
contacto@laparaups.com
REV 01 · 2026-07 · EN
LA-HR1235W
01 / 02
Technical specifications
SERIE LA-HR1235W | AGM BATTERY
MODEL
LA-HR1235W
| HIGH RATE AGM BATTERY |
| Model | LA-HR1235W |
| Nominal voltage | 12 V (6 cells per unit) |
| 15-minute capacity | 35 W |
| Nominal capacity | 9,0 Ah |
| Float service life | 5 years at 25°C |
| CONSTRUCTION |
| Positive / negative plate | Lead dioxide / lead |
| Electrolyte / separator | Sulphuric acid / glass fibre |
| Safety valve / terminal | EPDM / copper |
| Container | ABS (UL94-HB) / flame-retardant ABS (UL94-V0) |
| ELECTRICAL DATA |
| Internal resistance | Aprox. 16,7 mΩ a 25°C (±15%) |
| Maximum charging current | 2,7 A |
| Maximum discharge current | 140 A (5 s) |
| Short-circuit current | 430 A |
| CAPACITY AT 25°C |
| 15-minute rate | 35,0 W |
| 1-hour rate | 6,00 Ah |
| 3-hour rate | 7,23 Ah |
| 20-hour rate | 9,16 Ah |
| OPERATING TEMPERATURE |
| Nominal temperature | 25°C (77°F) |
| Discharge | -15°C ~ 50°C |
| Charge / storage | -15°C ~ 40°C |
| Capacity vs temperature (20 h) | 40°C: 102% · 25°C: 100% · 0°C: 85% · -15°C: 65% |
| CHARGING METHOD AT 25°C |
| Float charging | 13,5 ~ 13,8 VDC (-3 mV/celda/°C) |
| Equalisation charging | 14,1 ~ 14,4 VDC (-4 mV/celda/°C) |
| Cyclic use | 14,4 ~ 15,0 VDC (-5 mV/celda/°C) |
| PHYSICAL DATA |
| Dimensions, L x W x H (mm) | 151 x 65 x 94 (100 with terminal) |
| Terminal | F2 (Faston 6,3 mm) |
| Approximate weight | 2,46 kg (±3%) |
| STANDARDS |
| Standards / certifications | IEC, BS, JIS and Eurobat · UL (MH62092) and CE |
* Specifications subject to change without notice. Please refer to the applicable service conditions.
www.laparaups.com
contacto@laparaups.com
LA-HR1235W