DATASHEET
LA-ON-RACK-V.10
REV 01 · 2026-07 · EN
ONLINE RACK UPS · SERIE LA-ON-RACK-V.10
Continuous power
for critical systems
Double conversion, rack format and expansion with external battery banks.
SERIE  LA-ON-RACK-V.10
Online double conversion
TECHNOLOGY
2 models
LA-ON-6K · 10K RACK-V.10
Rack 19"
FORMAT
IDEAL FOR
Data centers
Technical rooms
Telecom
Critical loads
QUICK DECISION
The essentials, at a glance
Key figures for the range
POWER
6 / 10 kVA
POWER FACTOR
1
OUTPUTS
Terminal Block
COMMUNICATION
USB + RS-232
Optional SNMP · AS400 · ModBus
TECHNICAL ADVANTAGES
Key features
●  True double-conversion online UPS
●  Output power factor 1
●  Ready for connection of external battery banks
●  Wide input voltage range (110-300 VAC)
●  DSP technology that guarantees high performance
●  High efficiency of up to 94 %
●  Active input power factor correction 0.99
●  50Hz/60Hz frequency converter mode
2-year electronics warranty
1-year battery warranty
Free pickup & return service
Only applicable in the Iberian Peninsula
www.laparaups.com
contacto@laparaups.com
REV 01 · 2026-07 · EN
LA-ON-RACK-V.10
01 / 02
Technical specifications
SERIE LA-ON-RACK-V.10  |  ONLINE RACK UPS
MODEL
LA-ON-6K-RACK-V.10
LA-ON-10K-RACK-V.10
LA-ON-RACK-V.10 SERIES UPS
CAPACITY*6000VA / 6000W10000VA / 10000W
INPUT
Voltage range (Line loss)110 - 300 VAC @ (0~60%) Load / 140 - 300 VAC @ (60~80%) Load / 176 - 300 VAC @ (80~100%) Load
Voltage range (Line recovery - low)Low line loss voltage + 10V
Voltage range (Line recovery - high)High line loss voltage - 10V
Frequency rangeProgrammable 46Hz ~ 54 Hz @ 50 Hz / 56Hz ~ 64 Hz @ 60 Hz
PhaseSingle phase with earth connection (phase + neutral)
Power factor≥ 0.99 at nominal voltage and 100% load
THDi< 4% at 100% load, <6 % at 50% load
OUTPUT
Output voltage (Low voltage transfer)Programmable 208/220/230/240VAC (default: 230 VAC)
AC voltage regulation (Battery mode)± 1%
Frequency range (Synchronized range)Programmable 46Hz ~ 54 Hz @ 50Hz / 56Hz ~ 64 Hz @ 60Hz
Frequency range (Battery mode)Programmable 50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz
Crest current ratio3:1
Harmonic distortion≤ 1 % @ 100% linear loads; ≤ 4 % @ 100% non-linear loads
Transfer time (Mains ↔ Battery)0 ms
Transfer time (Inverter ↔ Bypass)0 ms
Transfer time (Inverter ↔ ECO)< 10 ms
Waveform (Battery mode)Pure sine wave
EFFICIENCY
AC mode> 94%
ECO mode> 94%
BATTERY
Battery type12V / 7AH12V / 9AH
Quantity2020
Typical recharge time7 hours to recharge 90% capacity9 hours to recharge 90% capacity
Charging current1 A ± 10% (max.)
Charging volts(Number of batteries*13.65 V) ± 1%
INDICATORS
LCD displayUPS status, load level, battery level, input/output voltage, discharge time and fault conditions.
ALARMS
Battery modeSounding every 4 seconds
Low batterySounding every second
OverloadSounding twice every second
FaultContinuous sound
PHYSICAL DATA
UPS dimensions, D x W x H (mm)600 X 438 X 88 (2U)
Battery bank dimensions, D x W x H (mm)600 X 438 X 138 (3U)
Net weight (kg) (UPS)13,50 Kg16 Kg
Net weight (kg) (Battery bank)55 kg63 kg
ENVIRONMENTAL CONDITIONS
Humidity<95 % non-condensing
Operating temperature0 ~ 40°C (battery life is reduced at temp. > 25°C)
**Operating altitude<1000m
Noise level< 55dB @ 1 meter
MANAGEMENT SOFTWARE
Smart RS-232 & USBSupports Windows 2000/2003/XP/Vista/2008/7/8/10, Linux, Unix and Mac
Optional SNMPPower management from the SNMP manager and web browser.
* Specifications subject to change without notice. Please refer to the applicable service conditions.
www.laparaups.com
contacto@laparaups.com
LA-ON-RACK-V.10