DATASHEET
LA-ON-LCD-V.10
REV 01 · 2026-07 · EN
ONLINE UPS · SERIE LA-ON-LCD-V.10
Power and control
in double conversion
High-performance online protection with adjustable charging and external bank connection.
SERIE  LA-ON-LCD-V.10
Online double conversion
TECHNOLOGY
2 models
LA-ON-6K · 10K LCD-V.10
Tower
FORMAT
IDEAL FOR
Data centers
Medical equipment
Telecom
Industry
QUICK DECISION
The essentials, at a glance
Key figures for the range
POWER
6 / 10 kVA
POWER FACTOR
1
OUTPUTS
Terminal Block
COMMUNICATION
USB + RS-232
Optional SNMP · AS400 · ModBus
TECHNICAL ADVANTAGES
Key features
●  True double conversion
●  DSP technology ensures high performance
●  Output power factor 1
●  High efficiency of up to 94%
●  50 Hz/60 Hz frequency converter mode
●  Emergency power off (EPO) function
●  Generator compatible
●  USB / RS-232 communications / Optional SNMP, ModBus, AS400
2-year electronics warranty
1-year battery warranty
Free pickup & return service
Only applicable in the Iberian Peninsula
www.laparaups.com
contacto@laparaups.com
REV 01 · 2026-07 · EN
LA-ON-LCD-V.10
01 / 02
Technical specifications
SERIE LA-ON-LCD-V.10  |  ONLINE UPS
MODEL
LA-ON-6K-LCD-V.10
LA-ON-10K-LCD-V.10
CAPACITY*6000VA / 6000W10000VA / 10000W
INPUT
Nominal voltage208/220/230/240 VAC (default: 230 VAC)
Voltage range110~300VAC ± 3% at 50% load; 176~300VAC ± 3% at 100% load
Voltage frequency46~54 Hz or 56~64 Hz
Frequency range46Hz ~ 54Hz @ 50Hz / 56Hz ~ 64Hz @ 60Hz
PhaseSingle-phase with ground (line + neutral)
Power factor≧ 0.99 at nominal voltage and 100% load
THDi< 4% at 100% load, < 6% at 50% load
OUTPUT
Output voltageProgrammable 208/220/230/240VAC (default: 230 VAC)
AC voltage regulation (Battery mode)± 1%
Frequency range (Synchronized range)Programmable 46Hz ~ 54Hz @ 50Hz / 56Hz ~ 64Hz @ 60Hz
Frequency range (Battery mode)Programmable 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
Crest factor3:1 (max)
Harmonic distortion≦ 1% @ 100% THD linear loads; ≦ 4% @ 100% THD non-linear loads
Transfer time (Mains ↔ Battery)0 ms
Transfer time (Inverter ↔ Bypass)0 ms
Transfer time (Inverter ↔ ECO)< 10 ms
Waveform (Battery mode)Pure sine wave
Overload (AC mode)100%~110%: 10min ; 110%~130%: 1min ; >130%: 1sec
Overload (Battery mode)100%~110%: 30sec ; 110%~130%: 10sec ; >130%: 1sec
EFFICIENCY
AC mode> 94%
Battery mode> 91%
BATTERY
Battery type12V / 7AH12V / 9AH
Quantity2020
Charge current4 A ± 10% (max.)
Charging voltage(Number of batteries * 13.65 V) ± 1%
INDICATORS
LCD displayUPS status, load level, battery level, input/output voltage, discharge time and fault conditions.
ALARMS
Battery modeSounding every 4 seconds
Low batterySounding every second
OverloadSounding twice every second
FaultContinuous sound
PHYSICAL DATA
Standard model (Dimensions, D x W x H)592 X 250 X 576 (mm)
Standard model (Net weight, kg)66,50 kg83 kg
ENVIRONMENTAL CONDITIONS
Humidity20-95% RH @ 0-40°C non-condensing
Operating temperature0 ~ 40°C (battery life is reduced at temp. > 25°C)
**Operating altitude<1000m
Noise level< 55dB @ 1 metro< 58dB @ 1 metro
MANAGEMENT SOFTWARE
Smart RS-232 & USBSupports Windows 2000/2003/XP/Vista/2008/7/8/10, Linux, Unix and Mac
Optional SNMPPower management from SNMP manager and web browser.
* Specifications subject to change without notice. Please refer to the applicable service conditions.
www.laparaups.com
contacto@laparaups.com
LA-ON-LCD-V.10