DATASHEET
LA-ON-LCD-V.10
REV 01 · 2026-07 · EN
ONLINE UPS · SERIE LA-ON-LCD-V.10Professional protection
with power factor 1
True double conversion, wide input range and advanced battery management.
Online double conversion
TECHNOLOGY
3 models
LA-ON-1K · 2K · 3K LCD-V.10
Tower
FORMAT
IDEAL FOR
Servers
Telecom
Medical equipment
Critical loads
QUICK DECISIONThe essentials, at a glance
Key figures for the range
POWER
1 - 3 kVA
POWER FACTOR
1
OUTPUTS
IEC C13/C19
COMMUNICATION
USB + RS-232
Optional SNMP · AS400 · ModBus
TECHNICAL ADVANTAGESKey features
● True double-conversion online UPS
● Microprocessor control for optimized reliability
● Output power factor 1
● Input power factor correction
● Wide input voltage range (110V - 300V)
● Optional ECO mode operation for energy saving
● Emergency power off (EPO) function
● Built-in overvoltage cut-off protection and MOV surge immunity for full-time equipment protection
3-year electronics warranty
2-year battery warranty
Free pickup & return service
Only applicable in the Iberian Peninsula
www.laparaups.com
contacto@laparaups.com
REV 01 · 2026-07 · EN
LA-ON-LCD-V.10
01 / 02
Technical specifications
SERIE LA-ON-LCD-V.10 | ONLINE UPS
MODEL
LA-ON-1K-LCD-V.10
LA-ON-2K-LCD-V.10
LA-ON-3K-LCD-V.10
| CAPACITY* | 1000VA / 1000W | 2000VA / 2000W | 3000VA / 3000W |
| INPUT |
| Voltage range (Low mains voltage transfer) | 160VAC/140VAC/120VAC/110VAC ± 5% or 80VAC/70VAC/60VAC/55VAC ± 5% (based on load percentage 100% - 80% / 80% - 70% / 70% - 60% / 60% - 0) |
| Voltage range (Low mains voltage return) | 175VAC/155VAC/135VAC/125VAC ± 5% or 87VAC/77VAC/67VAC/62VAC ± 5% |
| Voltage range (High mains voltage transfer) | 300 VAC ± 5% or 150 VAC ± 5% |
| Voltage range (High mains voltage return) | 290 VAC ± 5% or 145 VAC ± 5% |
| Frequency range | 40Hz ~ 70Hz |
| Phase | Single-phase with ground (line + neutral) |
| Power factor | ≧ 0.99 at nominal voltage and 100% load |
| THDi | ≦ 5% @ 205-245 VAC or 100 ~ 130 VAC; THDU < 1.6% @ linear load and charged battery |
| OUTPUT |
| Output voltage | 200/208/220/230/240 VAC or 100/110/115/120/127 VAC (default: 230 VAC) |
| AC voltage regulation (Battery mode) | ± 1% |
| Frequency range (Synchronized range) | 47~53Hz or 57~63Hz |
| Frequency range (Battery mode) | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz |
| Crest factor | 3:1 |
| Harmonic distortion | ≦ 2% THD (linear load); ≦ 4% THD (non-linear load) |
| Transfer time (AC mode to Battery mode) | Zero |
| Transfer time (Inverter to Bypass) | 4 ms |
| Waveform (Battery mode) | Pure sine wave |
| EFFICIENCY |
| AC mode | 89% @ charged battery | 91% @ charged battery | 91% @ charged battery |
| ECO mode | 96% @ charged battery |
| Battery mode | ≥ 88% | ≥ 90% | ≥ 90% |
| BATTERY |
| Battery type | 12V / 7AH | 12V / 7AH | 12V / 9AH |
| Quantity | 3 | 6 | 6 |
| Typical recharge time | 3 hours to recover 95% of capacity at 2A charge current |
| Charge current | 100/110/115/120/127 VAC models: default 2A, adjustable up to 8A; 200/208/220/230/240 VAC models: default 2A, adjustable up to 12A | Default: 2A, max: adjustable up to 8A | Default: 2A, max: adjustable up to 8A |
| Charging voltage | 41.0 VDC ± 1% | 82.1 VDC ± 1% | 82.1 VDC ± 1% |
| CONNECTIONS |
| Power outlets | 4xIEC C13 | 8xIEC C13 | 8xIEC C13 + 1xIEC C19 |
| Communication ports | 1xUSB + 1xRS232 + 1x SNMP intelligent slot |
| PHYSICAL DATA |
| Dimensions, D x W x H (mm) | 397 X 145 X 220 | 421 X 190 X 318 | 421 X 190 X 318 |
| Net weight with batteries (kg) | 12,90 | 22,80 | 27,00 |
| Net weight without batteries (kg) | 6.6 | 9.9 | 12.3 |
| OPERATING ENVIRONMENT |
| Humidity | 20-95% RH @ 0-40°C (non-condensing) |
| Noise level | < 50dBA @ 1 meter (with fan speed control) |
| MANAGEMENT SOFTWARE |
| Smart RS-232 & USB | Supports Windows 2000/2003/XP/Vista/2008/7/8/10, Linux, Unix and Mac |
| Optional SNMP | Power management from SNMP manager and web browser. |
* Specifications subject to change without notice. Please refer to the applicable service conditions.
www.laparaups.com
contacto@laparaups.com