DATASHEET
LA-ON-LCD-V.10
REV 01 · 2026-07 · EN
ONLINE UPS · SERIE LA-ON-LCD-V.10
Professional protection
with power factor 1
True double conversion, wide input range and advanced battery management.
SERIE  LA-ON-LCD-V.10
Online double conversion
TECHNOLOGY
3 models
LA-ON-1K · 2K · 3K LCD-V.10
Tower
FORMAT
IDEAL FOR
Servers
Telecom
Medical equipment
Critical loads
QUICK DECISION
The essentials, at a glance
Key figures for the range
POWER
1 - 3 kVA
POWER FACTOR
1
OUTPUTS
IEC C13/C19
COMMUNICATION
USB + RS-232
Optional SNMP · AS400 · ModBus
TECHNICAL ADVANTAGES
Key features
●  True double-conversion online UPS
●  Microprocessor control for optimized reliability
●  Output power factor 1
●  Input power factor correction
●  Wide input voltage range (110V - 300V)
●  Optional ECO mode operation for energy saving
●  Emergency power off (EPO) function
●  Built-in overvoltage cut-off protection and MOV surge immunity for full-time equipment protection
3-year electronics warranty
2-year battery warranty
Free pickup & return service
Only applicable in the Iberian Peninsula
www.laparaups.com
contacto@laparaups.com
REV 01 · 2026-07 · EN
LA-ON-LCD-V.10
01 / 02
Technical specifications
SERIE LA-ON-LCD-V.10  |  ONLINE UPS
MODEL
LA-ON-1K-LCD-V.10
LA-ON-2K-LCD-V.10
LA-ON-3K-LCD-V.10
CAPACITY*1000VA / 1000W2000VA / 2000W3000VA / 3000W
INPUT
Voltage range (Low mains voltage transfer)160VAC/140VAC/120VAC/110VAC ± 5% or 80VAC/70VAC/60VAC/55VAC ± 5% (based on load percentage 100% - 80% / 80% - 70% / 70% - 60% / 60% - 0)
Voltage range (Low mains voltage return)175VAC/155VAC/135VAC/125VAC ± 5% or 87VAC/77VAC/67VAC/62VAC ± 5%
Voltage range (High mains voltage transfer)300 VAC ± 5% or 150 VAC ± 5%
Voltage range (High mains voltage return)290 VAC ± 5% or 145 VAC ± 5%
Frequency range40Hz ~ 70Hz
PhaseSingle-phase with ground (line + neutral)
Power factor≧ 0.99 at nominal voltage and 100% load
THDi≦ 5% @ 205-245 VAC or 100 ~ 130 VAC; THDU < 1.6% @ linear load and charged battery
OUTPUT
Output voltage200/208/220/230/240 VAC or 100/110/115/120/127 VAC (default: 230 VAC)
AC voltage regulation (Battery mode)± 1%
Frequency range (Synchronized range)47~53Hz or 57~63Hz
Frequency range (Battery mode)50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
Crest factor3:1
Harmonic distortion≦ 2% THD (linear load); ≦ 4% THD (non-linear load)
Transfer time (AC mode to Battery mode)Zero
Transfer time (Inverter to Bypass)4 ms
Waveform (Battery mode)Pure sine wave
EFFICIENCY
AC mode89% @ charged battery91% @ charged battery91% @ charged battery
ECO mode96% @ charged battery
Battery mode≥ 88%≥ 90%≥ 90%
BATTERY
Battery type12V / 7AH12V / 7AH12V / 9AH
Quantity366
Typical recharge time3 hours to recover 95% of capacity at 2A charge current
Charge current100/110/115/120/127 VAC models: default 2A, adjustable up to 8A; 200/208/220/230/240 VAC models: default 2A, adjustable up to 12ADefault: 2A, max: adjustable up to 8ADefault: 2A, max: adjustable up to 8A
Charging voltage41.0 VDC ± 1%82.1 VDC ± 1%82.1 VDC ± 1%
CONNECTIONS
Power outlets4xIEC C138xIEC C138xIEC C13 + 1xIEC C19
Communication ports1xUSB + 1xRS232 + 1x SNMP intelligent slot
PHYSICAL DATA
Dimensions, D x W x H (mm)397 X 145 X 220421 X 190 X 318421 X 190 X 318
Net weight with batteries (kg)12,9022,8027,00
Net weight without batteries (kg)6.69.912.3
OPERATING ENVIRONMENT
Humidity20-95% RH @ 0-40°C (non-condensing)
Noise level< 50dBA @ 1 meter (with fan speed control)
MANAGEMENT SOFTWARE
Smart RS-232 & USBSupports Windows 2000/2003/XP/Vista/2008/7/8/10, Linux, Unix and Mac
Optional SNMPPower management from SNMP manager and web browser.
* Specifications subject to change without notice. Please refer to the applicable service conditions.
www.laparaups.com
contacto@laparaups.com
LA-ON-LCD-V.10