CSB GP1245 BATTERY

CSB GP1245 12V 4.5Ah battery designed for backup and general purpose applications, featuring sealed VRLA technology, maintenance-free operation, and high efficiency. It offers up to 5 years of standby service or over 260 cycles at 100% discharge, making it a reliable solution for power and security systems.

Categories: , Tag:
✓12V 4.5Ah general purpose VRLA battery
✓Up to 5 years service life in standby use
✓Over 260 cycles at 100% discharge in cyclic use
✓Rechargeable, high efficiency, sealed, leak-proof and maintenance-free
✓Maximum discharge current of 60A/90A for 5 seconds
✓Faston F1/F2 Tab187/250 terminals
✓ABS case with UL 94-V0 flame retardant material option upon request
✓ISO 9001 and ISO 14001 certified and UL 924 and UL 1989 recognized
CSB GP1245 12V 4.5Ah Battery

Parameter GP1245
Product General purpose VRLA battery
Model GP1245
Voltage per unit 12V
Cells per unit 6
Capacity 4.5Ah @ 20hr-rate to 1.75V per cell @25°C (77°F)
Approx. weight 1.66 kg (3.66 lbs)
Max. discharge current 60A / 90A (5 sec)
Internal resistance Approx. 40.5 mΩ
OPERATING TEMPERATURE
Discharge -15°C ~ 50°C (5°F ~ 122°F)
Charge -15°C ~ 40°C (5°F ~ 104°F)
Storage -15°C ~ 40°C (5°F ~ 104°F)
Nominal operating temperature 25°C ± 3°C (77°F ± 5°F)
CHARGING
Float charging voltage 13.5 to 13.8 VDC/unit average at 25°C (77°F)
Max. recommended current 1.35A
Equalization / cycle service voltage 14.4 to 15.0 VDC/unit average at 25°C (77°F)
Cycle charge per cell 2.45 V/cell (range 2.40 ~ 2.50)
Standby charge per cell 2.275 V/cell (range 2.25 ~ 2.30)
Max. charge current 0.3C
OTHER TECHNICAL DATA
Self-discharge Can be stored for more than 6 months at 25°C (77°F); recharge before use. At higher temperatures the interval will be shorter
Terminal F1/F2 - Faston Tab187/250
Container material ABS (UL 94-HB / File E50263). UL 94-V0 resistance / File E88637 available upon request
DIMENSIONS
Total height (H) 108 ± 1.5 mm
Container height (h) 102 ± 1.5 mm
Length (L) 92.8 ± 1 mm
Width (W) 69.9 ± 1 mm
CERTIFICATIONS
Approvals UL 924, UL 1989
Certifications ISO 9001, ISO 14001

GENERAL
Product
General purpose VRLA battery
Model
GP1245
Voltage per unit
12V
Cells per unit
6
Capacity
4.5Ah @ 20hr-rate to 1.75V per cell @25°C (77°F)
Approx. weight
1.66 kg (3.66 lbs)
Max. discharge current
60A / 90A (5 sec)
Internal resistance
Approx. 40.5 mΩ
OPERATING TEMPERATURE
Discharge
-15°C ~ 50°C (5°F ~ 122°F)
Charge
-15°C ~ 40°C (5°F ~ 104°F)
Storage
-15°C ~ 40°C (5°F ~ 104°F)
Nominal operating temperature
25°C ± 3°C (77°F ± 5°F)
CHARGING
Float charging voltage
13.5 to 13.8 VDC/unit average at 25°C (77°F)
Max. recommended current
1.35A
Equalization / cycle service voltage
14.4 to 15.0 VDC/unit average at 25°C (77°F)
Cycle charge per cell
2.45 V/cell (range 2.40 ~ 2.50)
Standby charge per cell
2.275 V/cell (range 2.25 ~ 2.30)
Max. charge current
0.3C
OTHER TECHNICAL DATA
Self-discharge
Can be stored for more than 6 months at 25°C (77°F); recharge before use
Terminal
F1/F2 - Faston Tab187/250
Container material
ABS (UL 94-HB). UL 94-V0 option upon request
DIMENSIONS
Total height (H)
108 ± 1.5 mm
Container height (h)
102 ± 1.5 mm
Length (L)
92.8 ± 1 mm
Width (W)
69.9 ± 1 mm
CERTIFICATIONS
Approvals
UL 924, UL 1989
Certifications
ISO 9001, ISO 14001