✓12V 34W sealed VRLA battery designed for backup applications
✓Up to 5 years service life in standby at 25°C
✓AGM technology for gas recombination of up to 99%
✓Maintenance-free battery for standby applications
✓34W rated power at 15 minutes to 1.67V per cell at 25°C
✓Maximum discharge current of 130A for 5 seconds
✓Maximum charging current of 3.4A
✓F2 Faston Tab250 terminal and ABS case with flame retardant option
✓Designed according to IEC 61056-1/2:2012
HR1234W 12V 34W Battery

Parameter HR1234W
Product Valve Regulated Lead Acid (VRLA) Battery
Series HR Series
Model HR1234W
Nominal voltage 12V (6 cells per unit)
Nominal capacity 34W @15min-rate to 1.67V per cell @25°C (77°F)
Design life Up to 5 years in standby at 25°C
Eurobat 3-5 years, Standard Commercial
ELECTRICAL SPECIFICATIONS
Maximum discharge current 130A (5 sec)
Short circuit current 349A
Internal resistance Approx. 19.0 mΩ
Maximum charging current 3.4A
CHARGING
Float charging voltage 13.5 ~ 13.8 VDC/unit at 25°C (77°F)
Equalization charging voltage 14.4 ~ 15.0 VDC/unit at 25°C (77°F)
Self-discharge Less than 10% after 90 days; can be stored up to 6 months at 25°C; recharge before use and sooner if stored at higher temperature
OPERATING TEMPERATURE
Nominal operating temperature 25°C (77°F)
Discharge -15°C ~ 50°C (5°F ~ 122°F)
Charge -15°C ~ 40°C (5°F ~ 104°F)
Storage -15°C ~ 40°C (5°F ~ 104°F)
PHYSICAL DATA
Weight Approx. 2.50 kg (5.51 lbs)
Length (L) 150.9 ± 2.0 mm
Width (W) 64.8 ± 1.0 mm
Container height (h) 94.3 ± 1.0 mm
Total height (H) 98.6 ± 1.0 mm
Terminal type F2 - Faston Tab250
Terminal torque --
Container material ABS (UL 94-HB) and flame retardant (94-V0) available on request
OTHER DATA
Technology AGM (Absorbent Glass Mat)
Design standard IEC 61056-1/2:2012
Certifications UL 1989, ISO 9001, ISO 14001

GENERAL
Product
Valve Regulated Lead Acid (VRLA) Battery
Series
HR Series
Model
HR1234W
Nominal voltage
12V (6 cells per unit)
Nominal capacity
34W @15min-rate to 1.67V per cell @25°C (77°F)
Design life
Up to 5 years in standby at 25°C
Eurobat
3-5 years, Standard Commercial
ELECTRICAL SPECIFICATIONS
Maximum discharge current
130A (5 sec)
Short circuit current
349A
Internal resistance
Approx. 19.0 mΩ
Maximum charging current
3.4A
CHARGING
Float charging voltage
13.5 ~ 13.8 VDC/unit at 25°C (77°F)
Equalization charging voltage
14.4 ~ 15.0 VDC/unit at 25°C (77°F)
Self-discharge
Less than 10% after 90 days; storable up to 6 months at 25°C
OPERATING TEMPERATURE
Nominal operating temperature
25°C (77°F)
Discharge
-15°C ~ 50°C (5°F ~ 122°F)
Charge
-15°C ~ 40°C (5°F ~ 104°F)
Storage
-15°C ~ 40°C (5°F ~ 104°F)
PHYSICAL DATA
Weight
Approx. 2.50 kg (5.51 lbs)
Length (L)
150.9 ± 2.0 mm
Width (W)
64.8 ± 1.0 mm
Container height (h)
94.3 ± 1.0 mm
Total height (H)
98.6 ± 1.0 mm
Terminal type
F2 - Faston Tab250
Terminal torque
--
Container material
ABS (UL 94-HB) and flame retardant (94-V0) available on request
OTHER DATA
Technology
AGM (Absorbent Glass Mat)
Design standard
IEC 61056-1/2:2012
Certifications
UL 1989, ISO 9001, ISO 14001