CSB HR1234W BATTERY
CSB HR1234W 12V 34W battery designed for standby backup applications, featuring AGM technology and sealed maintenance-free VRLA construction, offering up to 5 years of service life, high discharge capacity, and reliable performance for emergency power, security, and energy backup systems
✓12V 34W sealed VRLA battery designed for backup applications
✓Up to 5 years service life in standby at 25°C
✓AGM technology for gas recombination of up to 99%
✓Maintenance-free battery for standby applications
✓34W rated power at 15 minutes to 1.67V per cell at 25°C
✓Maximum discharge current of 130A for 5 seconds
✓Maximum charging current of 3.4A
✓F2 Faston Tab250 terminal and ABS case with flame retardant option
✓Designed according to IEC 61056-1/2:2012
HR1234W 12V 34W Battery
| Parameter | HR1234W |
|---|---|
| Product | Valve Regulated Lead Acid (VRLA) Battery |
| Series | HR Series |
| Model | HR1234W |
| Nominal voltage | 12V (6 cells per unit) |
| Nominal capacity | 34W @15min-rate to 1.67V per cell @25°C (77°F) |
| Design life | Up to 5 years in standby at 25°C |
| Eurobat | 3-5 years, Standard Commercial |
| ELECTRICAL SPECIFICATIONS | |
| Maximum discharge current | 130A (5 sec) |
| Short circuit current | 349A |
| Internal resistance | Approx. 19.0 mΩ |
| Maximum charging current | 3.4A |
| CHARGING | |
| Float charging voltage | 13.5 ~ 13.8 VDC/unit at 25°C (77°F) |
| Equalization charging voltage | 14.4 ~ 15.0 VDC/unit at 25°C (77°F) |
| Self-discharge | Less than 10% after 90 days; can be stored up to 6 months at 25°C; recharge before use and sooner if stored at higher temperature |
| OPERATING TEMPERATURE | |
| Nominal operating temperature | 25°C (77°F) |
| Discharge | -15°C ~ 50°C (5°F ~ 122°F) |
| Charge | -15°C ~ 40°C (5°F ~ 104°F) |
| Storage | -15°C ~ 40°C (5°F ~ 104°F) |
| PHYSICAL DATA | |
| Weight | Approx. 2.50 kg (5.51 lbs) |
| Length (L) | 150.9 ± 2.0 mm |
| Width (W) | 64.8 ± 1.0 mm |
| Container height (h) | 94.3 ± 1.0 mm |
| Total height (H) | 98.6 ± 1.0 mm |
| Terminal type | F2 - Faston Tab250 |
| Terminal torque | -- |
| Container material | ABS (UL 94-HB) and flame retardant (94-V0) available on request |
| OTHER DATA | |
| Technology | AGM (Absorbent Glass Mat) |
| Design standard | IEC 61056-1/2:2012 |
| Certifications | UL 1989, ISO 9001, ISO 14001 |
GENERAL
Product
Valve Regulated Lead Acid (VRLA) Battery
Series
HR Series
Model
HR1234W
Nominal voltage
12V (6 cells per unit)
Nominal capacity
34W @15min-rate to 1.67V per cell @25°C (77°F)
Design life
Up to 5 years in standby at 25°C
Eurobat
3-5 years, Standard Commercial
ELECTRICAL SPECIFICATIONS
Maximum discharge current
130A (5 sec)
Short circuit current
349A
Internal resistance
Approx. 19.0 mΩ
Maximum charging current
3.4A
CHARGING
Float charging voltage
13.5 ~ 13.8 VDC/unit at 25°C (77°F)
Equalization charging voltage
14.4 ~ 15.0 VDC/unit at 25°C (77°F)
Self-discharge
Less than 10% after 90 days; storable up to 6 months at 25°C
OPERATING TEMPERATURE
Nominal operating temperature
25°C (77°F)
Discharge
-15°C ~ 50°C (5°F ~ 122°F)
Charge
-15°C ~ 40°C (5°F ~ 104°F)
Storage
-15°C ~ 40°C (5°F ~ 104°F)
PHYSICAL DATA
Weight
Approx. 2.50 kg (5.51 lbs)
Length (L)
150.9 ± 2.0 mm
Width (W)
64.8 ± 1.0 mm
Container height (h)
94.3 ± 1.0 mm
Total height (H)
98.6 ± 1.0 mm
Terminal type
F2 - Faston Tab250
Terminal torque
--
Container material
ABS (UL 94-HB) and flame retardant (94-V0) available on request
OTHER DATA
Technology
AGM (Absorbent Glass Mat)
Design standard
IEC 61056-1/2:2012
Certifications