ONLINE UPS LA-ON-RACK-6-10K-V.10

Watch the product videoYouTube

Online UPS LA-ON-RACK-6-10K designed for high-power critical rack applications, with true double conversion, DSP technology, output power factor 1 and high efficiency, also featuring advanced management, compatibility with external battery banks, optional N+X parallel redundancy, and multiple communication interfaces for continuous, stable, professional electrical protection.


Online UPS LA-ON-RACK-6-10K

Categories: , Tag:
✓True double-conversion online UPS
✓Output power factor 1
✓Ready to connect external battery banks
✓Wide input voltage range (110–300 VAC)
✓DSP technology ensures high performance
✓High efficiency up to 94%
✓Active input power factor correction 0.99
✓Frequency converter mode 50 Hz/60 Hz
✓Emergency Power Off (EPO) function
✓Generator compatible
✓Adjustable number of batteries
✓Programmable ECO mode operation for energy saving
✓Overvoltage cut-off protection and MOV surge immunity
✓Multiple communication ports: SNMP (optional) + USB + RS-232
✓Optional N + X parallel redundancy
✓Optional OVCD protection

Description

High-capacity UPS with a high level of protection, capable of keeping your company running during possible power supply failures.

LA-ON-RACK-V.10 Series Online UPS

Model LA-ON-6K-RACK-V.10 LA-ON-10K-RACK-V.10
Capacity* 6000VA / 6000W 10000VA / 10000W
INPUT
Line loss 110–300 VAC @ (0–60%) load / 140–300 VAC @ (60–80%) load / 176–300 VAC @ (80–100%) load
Line recovery - low Low line-loss voltage + 10 V
Line recovery - high High line-loss voltage - 10 V
Frequency range Programmable 46 Hz–54 Hz @ 50 Hz / 56 Hz–64 Hz @ 60 Hz
Phase Single-phase with earth (phase + neutral)
Power factor ≧ 0.99 at nominal voltage and 100% load
THDi <4% at 100% load, <6% at 50% load
OUTPUT
Low-voltage transfer Programmable 208/220/230/240 VAC
AC voltage regulation (Battery mode) ± 1%
Frequency range (Synchronized range) Programmable 46 Hz–54 Hz @ 50 Hz / 56 Hz–64 Hz @ 60 Hz
Frequency range (Battery mode) Programmable 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
Crest factor 3:1
Harmonic distortion ≦ 1% @ 100% linear loads; ≦ 4% @ 100% non-linear loads
Mains ↔ Battery 0 ms
Inverter ↔ Bypass 0 ms
Inverter ↔ ECO <10 ms
Waveform (Battery mode) Pure sine wave
EFFICIENCY
AC mode >94%
ECO mode >94%
BATTERY
Battery type 12 V / 7 AH 12 V / 9 AH
Quantity 20 20
Typical recharge time 7 hours to recharge 90% capacity 9 hours to recharge 90% capacity
Charging current 1 A ± 10% (max.)
Charging voltage (Number of batteries*13.65 V) ± 1%
INDICATORS
LCD display UPS status, load level, battery level, input/output voltage, discharge time, and fault conditions.
ALARMS
Battery mode Beep every 4 seconds
Low battery Beep every second
Overload Beep twice every second
Fault Continuous beep
PHYSICAL DATA
UPS dimensions D x W x H (mm) 600 x 438 x 88 (2U)
Battery bank dimensions D x W x H (mm) 600 x 438 x 138 (3U)
Net weight (kg) UPS 13.50 kg 16 kg
Net weight (kg) battery bank 55 kg 63 kg
ENVIRONMENTAL CONDITIONS
Humidity <95% non-condensing
Operating temperature 0–40°C (battery life is reduced at temp. >25°C)
Operating altitude <1000 m
Noise level <55 dB @ 1 m
SOFTWARE MANAGEMENT
Smart RS-232 & USB Supports Windows 2000/2003/XP/Vista/2008/7/8/10, Linux, Unix and Mac
Optional SNMP Power management via SNMP manager and web browser.

MODELS
Capacity*
6K RACK
6000VA / 6000W
10K RACK
10000VA / 10000W
INPUT
Line loss
110–300 VAC @ (0–60%) load / 140–300 VAC @ (60–80%) load / 176–300 VAC @ (80–100%) load
Line recovery - low
Low line-loss voltage + 10 V
Line recovery - high
High line-loss voltage - 10 V
Frequency range
Programmable 46 Hz–54 Hz @ 50 Hz / 56 Hz–64 Hz @ 60 Hz
Phase
Single-phase with earth (phase + neutral)
Power factor
≧ 0.99 at nominal voltage and 100% load
THDi
< 4% at 100% load, <6% at 50% load
OUTPUT
Low-voltage transfer
Programmable 208/220/230/240 VAC
AC voltage regulation (Battery mode)
± 1%
Frequency range (Synchronized range)
Programmable 46 Hz–54 Hz @ 50 Hz / 56 Hz–64 Hz @ 60 Hz
Frequency range (Battery mode)
Programmable 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
Crest factor
3:1
Harmonic distortion
≦ 1% @ 100% linear loads; ≦ 4% @ 100% non-linear loads
Mains ↔ Battery
0 ms
Inverter ↔ Bypass
0 ms
Inverter ↔ ECO
< 10 ms
Waveform (Battery mode)
Pure sine wave
EFFICIENCY
AC mode
> 94%
ECO mode
> 94%
BATTERY
Battery type
6K RACK
12 V / 7 AH
10K RACK
12 V / 9 AH
Quantity
6K RACK
20
10K RACK
20
Typical recharge time
6K RACK
7 hours to recharge 90% capacity
10K RACK
9 hours to recharge 90% capacity
Charging current
1 A ± 10% (max.)
Charging voltage
(Number of batteries*13.65 V) ± 1%
INDICATORS
LCD display
UPS status, load level, battery level, input/output voltage, discharge time, and fault conditions.
ALARMS
Battery mode
Beep every 4 seconds
Low battery
Beep every second
Overload
Beep twice every second
Fault
Continuous beep
PHYSICAL DATA
UPS dimensions D x W x H (mm)
600 x 438 x 88 (2U)
Battery bank dimensions D x W x H (mm)
600 x 438 x 138 (3U)
Net weight (kg) UPS
6K RACK
13.50 kg
10K RACK
16 kg
Net weight (kg) battery bank
6K RACK
55 kg
10K RACK
63 kg
ENVIRONMENTAL CONDITIONS
Humidity
<95% non-condensing
Operating temperature
0–40°C (battery life is reduced at temp. >25°C)
Operating altitude
<1000 m
Noise level
< 55 dB @ 1 m
SOFTWARE MANAGEMENT
Smart RS-232 & USB
Supports Windows 2000/2003/XP/Vista/2008/7/8/10, Linux, Unix and Mac
Optional SNMP
Power management via SNMP manager and web browser.

Documentation

PDF
Datasheet
PDF
EU Declaration of Conformity
PDF
RoHS declaration
PDF
Certificate of origin
PDF
User manual

Documents automatically generated in the page language.