ONLINE UPS LA-ON-SH-V.09
LA-ON-SH-V0.9 true double-conversion online UPS designed to ensure continuous and stable power in professional environments, featuring a 0.9 output power factor, wide input voltage range, ECO mode operation, generator compatibility, and multiple communication interfaces for reliable monitoring and advanced electrical continuity management.
![]()
✓True double-conversion online UPS
✓Microprocessor control for optimized reliability
✓0.9 output power factor
✓Input power factor correction
✓Wide input voltage (110V - 300V)
✓Optional ECO mode operation for energy saving
✓50/60Hz output frequency converter mode
✓Generator compatible
✓Communication ports: Intelligent slot + USB + RS-232
✓Display for easy monitoring and UPS status access
LA-ON-SH-V0.9 Series Online UPS
| Model | LA-ON-1K-SH-V.09 | LA-ON-2K-SH-V.09 | LA-ON-3K-SH-V.09 |
|---|---|---|---|
| Capacity* | 1000 VA / 900 W | 2000 VA / 1800 W | 3000 VA / 2700 W |
| INPUT | |||
| Low voltage line transfer | 90VAC/80VAC/70VAC/60VAC±5% or 180VAC/160VAC/140VAC/120VAC±5% (Ambient Temperature <35ºC) (based on % load: 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0) | ||
| Low voltage line recovery | 95VAC/85VAC/75VAC/65VAC or 175VAC/155VAC/135VAC/125VAC ± 5 % (Ambient Temperature<35ºC) (based on % load: 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0) | ||
| High voltage transfer | 145 VAC ± 5 % or 300 VAC ± 5 % | ||
| High voltage recovery | 140 VAC ± 5 % or 290 VAC ± 5 % | ||
| Frequency range | 40Hz ~ 70 Hz | ||
| Phase | Single phase with ground | ||
| Power factor | ≧ 0.99 @ nominal voltage (input voltage) | ||
| OUTPUT | |||
| Output voltage | 110/115/120/127VAC or 208/220/230/240VAC | ||
| AC voltage regulation | ±1% (Battery mode) | ||
| Frequency range | 47 ~ 53 Hz or 57 ~ 63 Hz (Synchronized range) | ||
| Frequency range (Battery mode) | 50 Hz ± 0.5 Hz or 60Hz ± 0.5 Hz | ||
| Overload | 105%~110%: UPS shuts down after 10 minutes in battery mode or switches to bypass mode when utility power is normal. 110%~130%: UPS shuts down after 1 minute in battery mode or switches to bypass mode when utility power is normal. >130%: UPS shuts down after 3 seconds in battery mode or switches to bypass mode when utility power is normal. | ||
| Crest factor | 3:1 | ||
| Harmonic distortion | ≦ 3 % THD (linear load); ≦ 6 % THD (non-linear load) | ||
| Transfer time AC to Battery mode | Zero | ||
| Inverter to Bypass | 4 ms (Typical) | ||
| Waveform (Battery mode) | Pure sine wave | ||
| EFFICIENCY | |||
| AC mode | 88% | 89% | 90% |
| Battery mode | 83% | 87% | 88% |
| BATTERY | |||
| Battery type | 12 V / 9 Ah | 12 V / 9 Ah | 12 V / 9 Ah |
| Quantity | 2 | 4 | 6 |
| Recharge time | 4 hours to 90% capacity (Typical) | ||
| Charging current | 1.0 A (max.) | ||
| Charging voltage | 27.4 VDC ± 1% | 54.7 VDC ±1% | 82.1 VDC ±1% |
| CONNECTIONS | |||
| Outlets | 3 x Schuko | 3 x Schuko | 4 x Schuko + Terminal Block |
| Communication ports | 1xUSB + 1xRS232 + 1xIntelligent port | ||
| PHYSICAL CHARACTERISTICS | |||
| Dimensions D×W×H (mm) | 282 x 145 x 220 | 397 x 145 x 220 | 421 x 190 x 318 |
| Net weight (kg) | 9.3 | 16.7 | 26.5 |
| ENVIRONMENTAL CONDITIONS | |||
| Relative humidity | 20-90 % RH @ 0-40°C (non-condensing) | ||
| Noise level | < 50dBA @ 1 meter | ||
| MANAGEMENT | |||
| Smart RS-232 or USB | Supports Windows® 2000/2003/XP/Vista/2008/7/8, Linux, Unix and MAC | ||
| Optional SNMP | Power management via SNMP manager and web browser | ||
MODELS
Capacity*
1K
1000 VA / 900 W
2K
2000 VA / 1800 W
3K
3000 VA / 2700 W
INPUT
Low voltage line transfer
90VAC/80VAC/70VAC/60VAC±5% or 180VAC/160VAC/140VAC/120VAC±5% (Ambient Temperature <35ºC)
Low voltage line recovery
95VAC/85VAC/75VAC/65VAC or 175VAC/155VAC/135VAC/125VAC ± 5 % (Ambient Temperature<35ºC)
High voltage transfer
145 VAC ± 5 % or 300 VAC ± 5 %
High voltage recovery
140 VAC ± 5 % or 290 VAC ± 5 %
Frequency range
40Hz ~ 70 Hz
Phase
Single phase with ground
Power factor
≧ 0.99 @ nominal voltage (input voltage)
OUTPUT
Output voltage
110/115/120/127VAC or 208/220/230/240VAC
AC voltage regulation
±1% (Battery mode)
Frequency range
47 ~ 53 Hz or 57 ~ 63 Hz (Synchronized range)
Frequency range (Battery mode)
50 Hz ± 0.5 Hz or 60Hz ± 0.5 Hz
Overload
105%~110%: 10 min. / 110%~130%: 1 min. / >130%: 3 sec. in battery mode or bypass with normal utility
Crest factor
3:1
Harmonic distortion
≦ 3 % THD (linear load); ≦ 6 % THD (non-linear load)
Transfer time AC to Battery mode
Zero
Inverter to Bypass
4 ms (Typical)
Waveform (Battery mode)
Pure sine wave
EFFICIENCY
AC mode
1K
88%
2K
89%
3K
90%
Battery mode
1K
83%
2K
87%
3K
88%
BATTERY
Battery type
1K
12 V / 9 Ah
2K
12 V / 9 Ah
3K
12 V / 9 Ah
Quantity
1K
2
2K
4
3K
6
Recharge time
4 hours to 90% capacity (Typical)
Charging current
1.0 A (max.)
Charging voltage
1K
27.4 VDC ± 1%
2K
54.7 VDC ±1%
3K
82.1 VDC ±1%
CONNECTIONS
Outlets
1K
3 x Schuko
2K
3 x Schuko
3K
4 x Schuko + Terminal Block
Communication ports
1xUSB + 1xRS232 + 1xIntelligent port
PHYSICAL CHARACTERISTICS
Dimensions D×W×H (mm)
1K
282 x 145 x 220
2K
397 x 145 x 220
3K
421 x 190 x 318
Net weight (kg)
1K
9,3
2K
16,7
3K
26,5
ENVIRONMENTAL CONDITIONS
Relative humidity
20-90 % RH @ 0-40°C (non-condensing)
Noise level
< 50dBA @ 1 meter
MANAGEMENT
Smart RS-232 or USB
Supports Windows® 2000/2003/XP/Vista/2008/7/8, Linux, Unix and MAC
Optional SNMP
Power management via SNMP manager and web browser
Documentation
Documents automatically generated in the page language.


Technical datasheet
YouTube video