ONLINE UPS LA-ON-SH-V.09

LA-ON-SH-V0.9 true double-conversion online UPS designed to ensure continuous and stable power in professional environments, featuring a 0.9 output power factor, wide input voltage range, ECO mode operation, generator compatibility, and multiple communication interfaces for reliable monitoring and advanced electrical continuity management.



LA-ON-SH-V0.9 online UPS Icons

 

Categories: , Tag:
True double-conversion online UPS
Microprocessor control for optimized reliability
0.9 output power factor
Input power factor correction
Wide input voltage (110V - 300V)
Optional ECO mode operation for energy saving
50/60Hz output frequency converter mode
Generator compatible
Communication ports: Intelligent slot + USB + RS-232
Display for easy monitoring and UPS status access
LA-ON-SH-V0.9 Series Online UPS

Model LA-ON-1K-SH-V.09 LA-ON-2K-SH-V.09 LA-ON-3K-SH-V.09
Capacity* 1000 VA / 900 W 2000 VA / 1800 W 3000 VA / 2700 W
INPUT
Low voltage line transfer 90VAC/80VAC/70VAC/60VAC±5% or 180VAC/160VAC/140VAC/120VAC±5% (Ambient Temperature <35ºC) (based on % load: 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0)
Low voltage line recovery 95VAC/85VAC/75VAC/65VAC or 175VAC/155VAC/135VAC/125VAC ± 5 % (Ambient Temperature<35ºC) (based on % load: 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0)
High voltage transfer 145 VAC ± 5 % or 300 VAC ± 5 %
High voltage recovery 140 VAC ± 5 % or 290 VAC ± 5 %
Frequency range 40Hz ~ 70 Hz
Phase Single phase with ground
Power factor ≧ 0.99 @ nominal voltage (input voltage)
OUTPUT
Output voltage 110/115/120/127VAC or 208/220/230/240VAC
AC voltage regulation ±1% (Battery mode)
Frequency range 47 ~ 53 Hz or 57 ~ 63 Hz (Synchronized range)
Frequency range (Battery mode) 50 Hz ± 0.5 Hz or 60Hz ± 0.5 Hz
Overload 105%~110%: UPS shuts down after 10 minutes in battery mode or switches to bypass mode when utility power is normal. 110%~130%: UPS shuts down after 1 minute in battery mode or switches to bypass mode when utility power is normal. >130%: UPS shuts down after 3 seconds in battery mode or switches to bypass mode when utility power is normal.
Crest factor 3:1
Harmonic distortion ≦ 3 % THD (linear load); ≦ 6 % THD (non-linear load)
Transfer time AC to Battery mode Zero
Inverter to Bypass 4 ms (Typical)
Waveform (Battery mode) Pure sine wave
EFFICIENCY
AC mode 88% 89% 90%
Battery mode 83% 87% 88%
BATTERY
Battery type 12 V / 9 Ah 12 V / 9 Ah 12 V / 9 Ah
Quantity 2 4 6
Recharge time 4 hours to 90% capacity (Typical)
Charging current 1.0 A (max.)
Charging voltage 27.4 VDC ± 1% 54.7 VDC ±1% 82.1 VDC ±1%
CONNECTIONS
Outlets 3 x Schuko 3 x Schuko 4 x Schuko + Terminal Block
Communication ports 1xUSB + 1xRS232 + 1xIntelligent port
PHYSICAL CHARACTERISTICS
Dimensions D×W×H (mm) 282 x 145 x 220 397 x 145 x 220 421 x 190 x 318
Net weight (kg) 9.3 16.7 26.5
ENVIRONMENTAL CONDITIONS
Relative humidity 20-90 % RH @ 0-40°C (non-condensing)
Noise level < 50dBA @ 1 meter
MANAGEMENT
Smart RS-232 or USB Supports Windows® 2000/2003/XP/Vista/2008/7/8, Linux, Unix and MAC
Optional SNMP Power management via SNMP manager and web browser

MODELS
Capacity*
1K
1000 VA / 900 W
2K
2000 VA / 1800 W
3K
3000 VA / 2700 W
INPUT
Low voltage line transfer
90VAC/80VAC/70VAC/60VAC±5% or 180VAC/160VAC/140VAC/120VAC±5% (Ambient Temperature <35ºC)
Low voltage line recovery
95VAC/85VAC/75VAC/65VAC or 175VAC/155VAC/135VAC/125VAC ± 5 % (Ambient Temperature<35ºC)
High voltage transfer
145 VAC ± 5 % or 300 VAC ± 5 %
High voltage recovery
140 VAC ± 5 % or 290 VAC ± 5 %
Frequency range
40Hz ~ 70 Hz
Phase
Single phase with ground
Power factor
≧ 0.99 @ nominal voltage (input voltage)
OUTPUT
Output voltage
110/115/120/127VAC or 208/220/230/240VAC
AC voltage regulation
±1% (Battery mode)
Frequency range
47 ~ 53 Hz or 57 ~ 63 Hz (Synchronized range)
Frequency range (Battery mode)
50 Hz ± 0.5 Hz or 60Hz ± 0.5 Hz
Overload
105%~110%: 10 min. / 110%~130%: 1 min. / >130%: 3 sec. in battery mode or bypass with normal utility
Crest factor
3:1
Harmonic distortion
≦ 3 % THD (linear load); ≦ 6 % THD (non-linear load)
Transfer time AC to Battery mode
Zero
Inverter to Bypass
4 ms (Typical)
Waveform (Battery mode)
Pure sine wave
EFFICIENCY
AC mode
1K
88%
2K
89%
3K
90%
Battery mode
1K
83%
2K
87%
3K
88%
BATTERY
Battery type
1K
12 V / 9 Ah
2K
12 V / 9 Ah
3K
12 V / 9 Ah
Quantity
1K
2
2K
4
3K
6
Recharge time
4 hours to 90% capacity (Typical)
Charging current
1.0 A (max.)
Charging voltage
1K
27.4 VDC ± 1%
2K
54.7 VDC ±1%
3K
82.1 VDC ±1%
CONNECTIONS
Outlets
1K
3 x Schuko
2K
3 x Schuko
3K
4 x Schuko + Terminal Block
Communication ports
1xUSB + 1xRS232 + 1xIntelligent port
PHYSICAL CHARACTERISTICS
Dimensions D×W×H (mm)
1K
282 x 145 x 220
2K
397 x 145 x 220
3K
421 x 190 x 318
Net weight (kg)
1K
9,3
2K
16,7
3K
26,5
ENVIRONMENTAL CONDITIONS
Relative humidity
20-90 % RH @ 0-40°C (non-condensing)
Noise level
< 50dBA @ 1 meter
MANAGEMENT
Smart RS-232 or USB
Supports Windows® 2000/2003/XP/Vista/2008/7/8, Linux, Unix and MAC
Optional SNMP
Power management via SNMP manager and web browser

Documentation

PDF
Datasheet
PDF
EU Declaration of Conformity
PDF
RoHS declaration
PDF
Certificate of origin

Documents automatically generated in the page language.