Online UPS LA-ON-LCD-6-10K-LCD-V.10

The Online UPS LA-ON-LCD-6-10K-LCD-V.10 is designed for critical medium and high-power applications, featuring true double conversion, DSP technology, unity output power factor, and high efficiency up to 94%. It also incorporates advanced management, N+X parallel redundancy, professional communications, and adjustable load control for continuous and stable power protection.


 

Online UPS LA-ON-LCD-6-10K-LCD-V.10

Categories: , Tag:
True Double Conversion
DSP technology ensures high performance
Unity Output Power Factor
High efficiency up to 94%
Frequency converter mode 50 Hz/60 Hz
Emergency Power Off (EPO) function
Generator compatible
USB / RS-232 / Optional SNMP, ModBus, AS400 communications
Adjustable battery quantity
N+X Parallel Redundancy
Adjustable charging current via LCD panel
Hot Standby function compatible
LA-ON-LCD-V.10 On-Line UPS Series

Model LA-ON-6K-LCD-V.10 LA-ON-10K-LCD-V.10
Capacity* 6000VA / 6000W 10000VA / 10000W
INPUT
Nominal Voltage 208/220/230/240 VAC
Voltage Range 110~300VAC ± 3% at 50% load; 176~300VAC ± 3% at 100% load
Voltage Frequency 46~54 Hz or 56~64 Hz
Frequency Range 46Hz ~54 Hz @50 Hz / 56Hz ~ 64 Hz @60 Hz
Phase Single phase with ground (phase + neutral)
Power Factor ≧ 0.99 at nominal voltage and 100% load
THDi < 4% at 100% load, <6% at 50% load
OUTPUT
Output Voltage Programmable 208/220/230/240VAC
AC Voltage Regulation (Battery Mode) 1%
Frequency Range (Synchronized Range) Programmable 46Hz ~ 54 Hz @ 50Hz / 56Hz ~ 64 Hz @ 60Hz
Frequency Range (Battery Mode) Programmable 50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz
Crest Current Ratio 3:1 (max)
Harmonic Distortion ≦ 1% @ 100% THD linear loads; ≦ 4% @ 100% THD non-linear loads
Transfer Time Mains ↔ Battery 0 ms
Transfer Time Inverter ↔ Bypass 0 ms
Transfer Time Inverter ↔ ECO < 10 ms
Waveform (Battery Mode) Pure sine wave
Overload AC Mode 100%~110% 10min; 110%~130%: 1min; >130%: 1sec
Overload Battery Mode 100%~110%: 30sec; 110%~130%: 10sec; >130%: 1sec
EFFICIENCY
AC Mode > 94%
Battery Mode > 91%
BATTERY
Battery Type 12V / 7AH 12V / 9AH
Quantity 20 20
Charging Current 4 A ± 10% (max.)
Charging Voltage (Number of batteries*13.65 V) ± 1%
INDICATORS
LCD Display UPS status, load level, battery level, input/output voltage, discharge time, and fault conditions.
ALARMS
Battery Mode Beeps every 4 seconds
Low Battery Beeps every second
Overload Beeps twice every second
Fault Continuous beep
PHYSICAL DATA
Dimensions D x W x H 592 X 250 X 576 (mm)
Net Weight (kg) 66.50 kg 83 kg
ENVIRONMENTAL CONDITIONS
Humidity 20-95% RH @ 0-40°C non-condensing
Operating Temperature 0 ~ 40°C (battery life reduces with temp. > 25°C)
Operating Altitude <1000m
Noise Level < 55dB @ 1 Meter < 58dB @ 1 Meter
SOFTWARE MANAGEMENT
Smart RS-232 & USB Supports Windows 2000/2003/XP/Vista/2008/7/8/10, Linux, Unix, and Mac
Optional SNMP Power management from SNMP manager and web browser.

MODELS
Capacity*
6K
6000VA / 6000W
10K
10000VA / 10000W
INPUT
Nominal Voltage
208/220/230/240 VAC
Voltage Range
110~300VAC ± 3% at 50% load; 176~300VAC ± 3% at 100% load
Voltage Frequency
46~54 Hz or 56~64 Hz
Frequency Range
46Hz ~54 Hz @50 Hz / 56Hz ~ 64 Hz @60 Hz
Phase
Single phase with ground (phase + neutral)
Power Factor
≧ 0.99 at nominal voltage and 100% load
THDi
< 4% at 100% load, <6% at 50% load
OUTPUT
Output Voltage
Programmable 208/220/230/240VAC
AC Voltage Regulation (Battery Mode)
1%
Frequency Range (Synchronized Range)
Programmable 46Hz ~ 54 Hz @ 50Hz / 56Hz ~ 64 Hz @ 60Hz
Frequency Range (Battery Mode)
Programmable 50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz
Crest Current Ratio
3:1 (max)
Harmonic Distortion
≦ 1% @ 100% THD linear loads; ≦ 4% @ 100% THD non-linear loads
Mains ↔ Battery
0 ms
Inverter ↔ Bypass
0 ms
Inverter ↔ ECO
< 10 ms
Waveform (Battery Mode)
Pure sine wave
Overload AC Mode
100%~110% 10min; 110%~130%: 1min; >130%: 1sec
Overload Battery Mode
100%~110%: 30sec; 110%~130%: 10sec; >130%: 1sec
EFFICIENCY
AC Mode
> 94%
Battery Mode
> 91%
BATTERY
Battery Type
6K
12V / 7AH
10K
12V / 9AH
Quantity
6K
20
10K
20
Charging Current
4 A ± 10% (max.)
Charging Voltage
(Number of batteries*13.65 V) ± 1%
INDICATORS
LCD Display
UPS status, load level, battery level, input/output voltage, discharge time, and fault conditions.
ALARMS
Battery Mode
Beeps every 4 seconds
Low Battery
Beeps every second
Overload
Beeps twice every second
Fault
Continuous beep
PHYSICAL DATA
Dimensions D x W x H
592 X 250 X 576 (mm)
Net Weight (kg)
6K
66.50 kg
10K
83 kg
ENVIRONMENTAL CONDITIONS
Humidity
20-95% RH @ 0-40°C non-condensing
Operating Temperature
0 ~ 40°C (battery life reduces with temp. > 25°C)
Operating Altitude
<1000m
Noise Level
6K
< 55dB @ 1 Meter
10K
< 58dB @ 1 Meter
SOFTWARE MANAGEMENT
Smart RS-232 & USB
Supports Windows 2000/2003/XP/Vista/2008/7/8/10, Linux, Unix, and Mac
Optional SNMP
Power management from SNMP manager and web browser.

Documentation

PDF
Datasheet
PDF
EU Declaration of Conformity
PDF
RoHS declaration
PDF
Certificate of origin

Documents automatically generated in the page language.